On 29 December 2025, around seven in the morning, the industrial control systems of a Polish cogeneration plant serving roughly 50,000 residents were hit. A steam turbine stopped, and so did the plant’s process water treatment. Heat and electricity to end users were never cut; the on-site staff’s quick reaction kept the stoppage short. The operator first assumed a contractor error during maintenance and reported the event for information only. CERT Polska, already handling parallel incidents in the energy sector, treated it as an attack from the start, and the analysis proved them right. According to the team, it is the first time a private APN, the dedicated cellular network a distribution operator uses for remote control of its field equipment, has been observed as an access vector into an operational technology network in a real incident.

That detail alone deserves a pause. Had the plant kept quiet about an unexplained malfunction during maintenance, the episode would never have been connected to the wider campaign. The culture of notification does not only concern confirmed incidents. It concerns the boring events nobody wants to write up.

The reconstructed chain spans eleven steps, and it reads less like an elite operation than like a guided tour of defaults left untouched. It began at a wind farm substation whose perimeter device allowed VPN authentication with locally defined accounts and no multi-factor authentication. From that foothold the path reached a cellular router, a Teltonika model that exposes its administrative web interface and SSH service on the LAN side by default, and CERT Polska assesses it highly probable that SSH was used to open a tunnel into the private APN. Note the word probable: some links in the chain were not recovered from the victims’ systems but inferred by correlating the mobile operator’s logs with those available at the plant. Without that fourth party, much of the route would have stayed undemonstrable. This is reconstruction, not a confession.

Inside the APN sat a WAGO controller still presenting its administration interface on the wide-area side with the factory credentials of the admin account unchanged. That is the quiet scandal of the whole story. Not a zero-day, not an exotic exploit chain, but a device shipped with a default password that someone forgot to change, reachable on a network everyone assumed was private and therefore safe. A separate point of precision, because it matters: on the Teltonika router the default password had in fact been changed by the firm that performed the installation, and investigators could not establish how the attacker obtained access to it. The default-credentials problem belongs to the WAGO, not to everything in the chain.

From there came a week of reconnaissance across the plant network, probing for industrial protocols and remote-desktop services, and on 25 December successful connections to three Siemens PLCs. On 29 December, over a few hours, the controllers were placed in STOP and protected with a password, the turbine and water treatment were brought down, and more than ten devices, serial servers and network switches were reset to factory settings, given new passwords and assigned unreachable addresses such as 127.0.0.1 to stretch out recovery. The cadence of the requests points to automation. Restoration meant reloading backups of the control logic, effective on downtime but costing the logs that sat on the controllers, as Siemens ProductCERT confirmed. The attacker even corrupted the WAGO used as the doorway, so that the operator’s factory reset left it unbootable and no useful log survived. A meticulous erasing of one’s own footprints is itself a statement of intent.

So much for the technical tour. The part worth arguing about is the one written in contracts, not in config files. The distribution operator required that all communication with the remote terminal unit travel over a serial protocol, DNP3.0, and at the compromised site that requirement was met to the letter. No requirement at all had been defined for the administrative interface of the cellular router that carried that protocol. Read it again: the rule governed the cargo and ignored the truck. The intruder walked in precisely through that blank space in the contract, the gap between a formal requirement diligently satisfied and the real attack surface nobody had made anyone’s responsibility.

This is why the incident is not a Polish curiosity. CERT Polska found that the APN misconfiguration allowing arbitrary devices to talk to each other was commonly encountered in Poland and believes similar setups are widespread elsewhere; CISA judged the case relevant beyond national borders. The attack crossed three organisations, the wind farm, the distributor and the plant itself, and none of them had visibility over the whole infrastructure. The plant least of all: it was reached through infrastructure it did not control, another party’s perimeter and a private APN run by a third. Reconstruction was only possible by adding a fourth actor, the mobile network operator, whose logs filled in what the victims’ own systems could not document.

This is exactly the risk NIS2 points at when it talks about supply chain security and relationships between essential entities, under Article 21 of the directive, transposed in Italy by Legislative Decree 138 of 2024. The directive turns into a very concrete operational question: who answers for the configuration of a shared private APN, who has the contractual right to audit it, and who keeps the logs needed to reconstruct an incident that crosses three organisations. In the Polish experience, at the moment of the attack, the answer was: nobody had decided. The recommendations that follow, isolating clients on the APN, treating it as an untrusted network with segmentation equal to a corporate WAN, disabling exposed administrative interfaces, SSH and Telnet, changing default credentials, and bringing the APN inside penetration tests, are all sound. They are also the kind of advice that only sounds revelatory because the obvious was left undone.

Attribution, for what it is worth, remains contested: the Polish investigators themselves judged the available similarities too weak to conclude, and the follow-up report adds no attribution of its own. Treating a contested attribution as a settled fact would be its own small failure of rigour.

The uncomfortable question is the one the recommendations do not answer: why does it take a turbine stopping on a December morning to make a contract notice the interface it never mentioned? Supply chain security is not a technology problem to be solved with one more appliance. It is a question of who owns the risk when the risk lives in the space between organisations, on a network each one assumed belonged to someone else.